28
General tips
• DIP switch in OFF position as standard when supplied.
Obstacle recognition (DIP 1, 2 + 3)
DIP switch 1
OFF No response in the event of a safety input interruption.
In the event of a force cut-off, the door is halted.
ON Drive stops door
DIP switch 2: Safety contact strip
OFF Normally closed contact for light barrier
ON Push-button connection for push-button
(partial opening mode; defined opening and closing mode)
DIP switch 3: behaviour of drive when door is closing
OFF Drive stops and opens door a little (reversal)
ON Drive stops and opens door completely
Connecting button 2 (DIP 2)
Use the contact only for potential-free normally closed contacts.
External voltage may damage or even destroy the control unit.
No further safety connections are available.
Button 2 can be used in conjunction with the following functions:
- Preset opening and closing
- Partial opening
• Permissible cable cross-section: max. 0,75 mm².
Terminal 1 + 2 Push-button 2 connection, only if DIP switch 2 is ON.
Direct socket unit
• Permissible cable cross-section: max. 1,5 mm².
Terminal 1 + 2 Transformer
Terminal 3 C-rail
Terminal 4 Chain
Swap connections (terminals 3 + 4) around if drive is to be used in
conjunction with swing doors.
Use the contact only for potential-free normally closed contacts.
External voltage may damage or even destroy the control unit.
Terminal 5 + 6 Push-button connection (push-button 1);
vacant in duo's case.
potential-free NO contact
Drive behaviour upon closing the door
If the door meets an obstacle (force cut-off) or if the safety input is inter-
rupted (person triggering the light barrier), this is detected by the drive
system, depending on the position of the DIP switches 2 + 3.
Drive behaviour upon opening the door
If the door meets an obstacle (force cut-off) or if the safety input is inter-
rupted (person triggering the light barrier), this is detected by the drive sys-
tem, depending on the position of the DIP switch 1.
Connecting warning lamp (DIP 4)
• Permissible cable cross-section: max. 1,5 mm².
Terminal 5 + 6 Non-regulated 24 V/DC (max. 34 V),
21 watt, max. 1.0 A
DIP switch 4
OFF Connected warning lamp flashes (control unit generates flashing)
ON Door status indicator
- is lit when door is not closed
- is out when door is closed
Warning time (DIP 5)
The warning lamp starts to flash after push-button is pressed or manual
remote control operated during the three seconds before the drive starts up.
If the push-button is pressed again or the manual remote control is operat-
ed during the 3 seconds, the early warning period is ended prematurely.
The early warning period functions in conjunction with both internal lighting
and with a connected warning lamp.
DIP switch 5
OFF Deactivated
ON Activated; internal lighting and warning lamp flash for 3 seconds.
Backjump (DIP 6)
In vertical-sectional doors, you have the option of activating the
backjump with DIP switch 6 in order to offload the operator
system and the door. It also facilitates the activation of the
emergency release.
This feature serves the purpose of supporting door and drive mechanism
operation. The drive mechanism moves briefly back in a door OPEN direc-
tion once it has reached the door CLOSED final travel position, thus taking
some of the strain off the other equipment.
DIP switch 6
OFF Deactivated
ON Activated
Connecting light barrier
• Permissible cable cross-section: max. 0,75 mm².
Terminal 1 + 2 Safety connection, only if DIP switch 2 is OFF
Terminal 3 + 4 regulated 12 V DC, max. 0.1 A
Terminal 3: 24 V/DC
Terminal 4: Earth
Settings: see Obstacle Detection (DIP 1, 2 + 3)